| Nominal sensing distance | 5mm |
| Operanting distance | 0…4,05mm |
| Standard target | 18x18mm FE360 |
| Correction Factor | copper: 0,25 / aluminium: 0,35 / brass: 0,40 / stainless steel: 0,70 |
| Thermal drift of Sr | < 10% |
| Repeat Accuracy | < 5% (UB 24V Ta=23°C ±5°C) |
| Hysteresis | 1 … 20% |
| Description | M18 standard flush mount |
| Functions | Proximity |
| Output type | PNP |
| Output Function | NO |
| Switching frequency | 1,5kHz |
| Operating Voltage | 10...30Vdc |
| No-Load supply current | ≤ 15mA |
| Load current | ≤ 200mA |
| Leakage current | ≤ 10μA |
| Output voltage drop | ≤ 2V @200mA |
| Max ripple content | ≤ 10% |
| LED indicators | Yellow LED output state |
| Time delay before availability | ≤ 50ms |
| Short-circuit protection | Yes |
| Reverse Polarity Protection | Yes |
| Impulsive Overvoltage Protection | Yes |
| Protection against inductive loads | Yes |
| Mounting | Shielded |
| Dimensions | M18 x 1 / L = 63,1mm |
| Weight | 55g |
| Housing Material | AISI316L Stainless Steel |
| Connections | M12 Plug |
| Active Head Material | PPS |
| Tightening torque | 50Nm |
| Operating temperature | -40°C…+80°C (up to 100°C for short exposure during cleaning process) |
| Material | AISI316L Stainless Steel |
| Diameter/Dimension | M18 |
| Approvals | CE cULus ECOLAB DIVERSY |
| EMC compatibility | IEC 60947-5-2 |
| Shocks and vibrations | Vibration IEC 60068-2-6 / Shock IEC 60068-2-27 |
| Degree of protection | IP68, IP69K |
| Supplied Accessories | 2 nuts M18x1 |
| Dimensions | M18 x 1 / L = 63,1mm |
| Operating Temperature | -40°C…+80°C (up to 100°C for short exposure during cleaning process) |
| Mechanical Protection | IP67 |