| Nominal sensing distance | 1mm |
| Operanting distance | 0…0,81mm |
| Standard target | 8x8mm FE360 |
| Correction Factor | copper: 0,2…0,5 / aluminium: 0,3...0,5 / brass: 0,4...0,6 / stainelss steel: 0,7…0,9 |
| Repeat Accuracy | < 3% (UB 24V Ta=23°C ±5°C) |
| Hysteresis | < 10% |
| Description | D6.5 NAMUR flush mount |
| Functions | Proximity |
| Output type | NAMUR |
| Output Function | NAMUR |
| Switching frequency | 2kHz |
| Response time | 0,25 |
| Operating Voltage | 7,7...9Vdc |
| No-Load supply current | < 1mA (target absent) |
| Load current | < 3mA (target present) |
| Max ripple content | ≤ 10% |
| Short-circuit protection | Yes |
| Reverse Polarity Protection | Yes |
| Emission | ≥100kHz |
| Protection against inductive loads | Yes |
| Dimensions | Ø6.5x50 |
| Mounting | Shielded |
| Material | Nickel-plated brass |
| Housing material | Nickel-plated brass |
| Connections | M8 Plug |
| Active Head Material | LCP |
| Diameter/Dimension | Ø6,5 |
| Approvals | CE cULus |
| Dimensions | Ø6.5 / L = 50mm |
| Operating Temperature | -25°C…+60°C |
| Mechanical Protection | IP67 |