NAMUR

95B066310

IS-65-A20-S1

Non-contact detection Cost effective and reliable detection of any metal part

  • Standard proximity M4, M5, M8, M12, M18, M30
  • Double range (i.e. M12 4mm, M18 14mm, M30
  • 20mm)
  • Unshielded or shielded models for flush mounting
  • Nickel brass or stainless steel short and long
  • housing
  • Ecolab and Diversey certifications for industrial
  • detergents
  • Multi-voltage, Metal face, Weld field immune models
  • NO/NC, NPN or PNP output and programmable
  • versions.



Technical features

Detection properties

Nominal sensing distance 1mm
Operanting distance 0…0,81mm
Standard target 8x8mm FE360
Correction Factor copper: 0,2…0,5 / aluminium: 0,3...0,5 / brass: 0,4...0,6 / stainelss steel: 0,7…0,9
Repeat Accuracy < 3% (UB 24V Ta=23°C ±5°C)
Hysteresis < 10%

Application

Description D6.5 NAMUR flush mount
Functions Proximity

Outputs

Output type NAMUR
Output Function NAMUR
Switching frequency 2kHz
Response time 0,25

Electrical data

Operating Voltage 7,7...9Vdc
No-Load supply current < 1mA (target absent)
Load current < 3mA (target present)
Max ripple content ≤ 10%
Short-circuit protection Yes
Reverse Polarity Protection Yes
Emission ≥100kHz
Protection against inductive loads Yes

Mechanical data

Mounting Shielded
Dimensions Ø6.5x50
Housing Material Nickel-plated brass
Connections M8 Plug
Active Head Material LCP
Material Nickel-plated brass
Diameter/Dimension Ø6,5

Test/Approvals

Approvals CE cULus

Generical Data

Dimensions Ø6.5 / L = 50mm
Operating Temperature -25°C…+60°C
Mechanical Protection IP67